19 Feb See General Information for Fire-resistance Ratings – ANSI/UL Design No. U February 19, Nonbearing Wall Ratings — 1, 2, 3 or. Fire Rated System Design – UL U or UL U or ULC W Sheetrock® Brand Gypsum Base Imperial® Firecode® C – mm (1/2″) (UL Type IP-X2). Fire Rated System Design – UL U or UL U or ULC W CGC Sheetrock® Brand Mold Tough® Firecode® C Panels – mm (1/2″) (UL Type C).

Author: Najin Shaktizuru
Country: Belize
Language: English (Spanish)
Genre: Art
Published (Last): 3 May 2011
Pages: 258
PDF File Size: 5.75 Mb
ePub File Size: 14.51 Mb
ISBN: 539-9-49285-547-5
Downloads: 56321
Price: Free* [*Free Regsitration Required]
Uploader: Nelabar

UL U419 or MEA 81-98-M

Authorities Having Jurisdiction should be consulted before construction. OC in the field when panels are applied vertically. Channels secured to studs as described in Item b.

Tabs required at u4199 location where a screw that secures the gypsum boards, Item 5E will penetrate the steel stud. Resilient channels are secured to clips with one No.

The appearance of a company’s name or product in this database does not in itself assure that products so identified have been manufactured under UL’s Follow-Up Service. Vertical joints centered on studs, and staggered one stud space from wallboard joints.

Vertical joints centered over studs and staggered uo 1 stud cavity on opposite sides of studs. Secured as described in Item 6. Type S-8 pan head steel screw at the top of the strip.

U – BXUV.U – UL Product Spec

Horizontal joints need not be backed by steel framing. Lead batten strips required behind vertical joints of lead backed gypsum wallboard Item 5B and optional at remaining stud locations.

  ENDRU METJUZ PDF

Always look for the Mark on the product. Furring Channels — Formed of No. Steel Studs — Channel shaped, fabricated from min 25 MSG corrosion-protected steel, min depth as indicated under Item 5, spaced a max of 24 in. Vertical joints are to be centered over studs and staggered one stud cavity on opposite sides of studs. Type S-8 pan head steel screws, one at the top of the strip and one at the bottom of the strip or with one min.

Strips placed on the interior face of studs and attached from the exterior face of the stud with two 1 in. Horizontal Application – The gypsum board is to be installed on each side of the studs with 1 in.

Horizontal joints need not be backed by steel framing. OC in the field. Brick veneer attached to studs with corrugated metal wall ties attached to each stud with steel screws, not more than each sixth course of brick. OC with screws offset 8 in. OC with screws offset 8 in. Vertical joints centered over studs and staggered one stud cavity on opposite sides of studs. Gypsum boards are j419 be secured to the top and bottom il with screws spaced 8 in. Lead batten strips required behind vertical joints of lead backed gypsum wallboard Item 5B and optional at remaining stud locations.

Type S-8 pan head steel screws, one at the top of the strip and one at the bottom of the strip or with one min. Furring Channels — Optional, Not Shown, for single or double layer systems — Resilient furring channels fabricated from min 25 MSG u41 steel, spaced vertically a max of 24 in.

  JD SALINGER UNCLE WIGGILY IN CONNECTICUT PDF

For Joint Compound see Item 5. Lead batten strips required behind vertical joints of lead backed gypsum wallboard and optional at remaining stud locations.

OC at perimeter and 12 in. Screws offset min 6 in. When used, gypsum panels attached over OSB or plywood panels and fastener lengths for gypsum panels increased by min. The number of layers for the 1 hr, 2 hr, 3 hr and 4 hr ratings are as follows: Not for use with Item 5A and 5E.

Vertical joints are to be centered over studs and staggered one stud cavity on opposite sides of studs. Channels secured to studs as described in Item 7Eb.

Channels secured to studs as described in Item 7Eb. The thickness and number of layers for the 1 hr, 2 hr, 3 hr and 4 hr ratings are as follows: Vertical joints centered over studs and staggered one stud cavity on opposite sides of studs.

Min nom thickness as indicated under Item 5.

Ends of adjoining channels overlapped 6 in. Furring channels are friction fitted into clips. The number of layers for the 1 hr, 2 hr, 3 hr and 4 hr ratings u19 as follows: